PIKA Indoor
LoRaWAN Module
Installation Requirements for the Product Substrate and Powering Up
Specifications
LoRaWan Module PIKA is an easy and intelligent device dedicated to collecting data from on-site Modbus RTU / Modbus TCP/ Pulse devices, and transmitting them to the Internet via LoRaWAN. It can read up to 50 Modbus register addresses on 8 Modbus devices with the same configuration. Besides, PIKA supports configuring warning trigger values which can immediately send a Lora packet when Modbus data is out of settings.
Wireless Transmission
-
Technology:LoRaWAN
-
Antenna:Internal Antenna or External Antenna
-
Frequency :EU433, CN470, IN865, EU868, AU915, US915, KR920, RU864, and AS923-1/2/3/4
-
Tx Power:16dBm (923 MHz) Sensitivity :-137 dBm
Modbus Interface
-
Modbus RTU
-
Port :1 x RS485
-
Baud Rate:1200~115200 bps
-
Modbus TCP/IP
-
Port :1x RJ45 (Option)
Data Configuration
-
Port:1x Type C
-
Tool :PIKA PC Software
Pulse input
-
Port :Terminal Block 3.81mm
Others
-
Reset Button Internal
-
User Button
-
LED Indicator
-
Lora antenna
Physical Characteristics
-
Power Connector : Terminal Block 3.81mm
-
Power Supply :1. 6-24 VDC Terminal Block, 2. 5 VDC by type-C Port
-
Power Consumption :< 0.5W
-
Material & Color :PC+ABS, White
-
Ingress Protection:IP54
-
Operating Temperature :-20°C ~ 60°C (-4°F to +140°F)
-
Relative Humidity :0% ~ 95% (non-condensing)
-
Dimensions :124*67*34 mm
-
Installation:Wall Mounting
PIKA Software Features
PIKA device communication COM port setting (Serial port, Baud rate, Data bits, Parity bits, Stop bits).
Status
-
Model
-
Serial Number
-
Hardware version
-
Firmware version
-
LoRaWAN Enable
-
Device EUI
-
Join Mode
-
Join Status
-
Class
-
Regional Band
-
RSSI/SNR
-
Uplink Frame Counter
-
Report interval
-
Modbus TCP/IP
LoRaWAN setting
-
Enable / Disable LoRaWAN.
-
Regional Band (EU433, CN470, IN865, EU868, AU915, US915, KR920, RU864, and AS923-1/2/3/4) Default AS923-2.
-
Class (A, C).
-
Join Mode (OTAA/ABP)
-
Device EUI
-
Application EUI
-
Application Keys
-
Network ID
-
Device Address
-
Network Session Key
-
Application Session Key
-
Application Port
-
Frame Counter Up
-
Transmit Power
-
RX2 Frequency (Hz)
-
RX2 Data Rate
-
Adaptive Data Rate (ADR)
-
Data Rate
-
Confirm Mode
-
Send Retry
Modbus setting
-
Switch between Modbus RTU and Modbus TCP connection.
-
Import/Export CSV file.
-
Settings Modbus
-
Polling up to 8 slave ID.
-
Configuring up to 50 data fields.
-
Data field name, Offset address, Register address, Function code (03/04), Length, Data type (sign, unsign, INT16, INT32, INT64, float32, double64), Warning Type (warning with, warning without, warning range), Warning Value, 4 bytes data order, 8 bytes data order.
-
Poll data.
Modbus RTU setting
-
Baud rate (1200,2400,4800,9600,19200,38400,57600,115200)
-
Data bits (8,9)
-
Parity bits (None, Odd, Even)
-
Stop bits (0,1)
-
Execution interval (min)
-
Response Timeout (ms)
-
Delay Between Poll (ms)
-
Maximum Retry Times
-
Base Address (0,1)
-
Slave ID
Modbus TCP/IP setting
-
IP address
-
MAC Address
-
Subnet Mask
-
Gateway Address
-
Port (502)
-
Connection timeout
Pulse setting
-
Number of Cubic Meter Digits
-
Number of Liters Digits
-
Set New Value
-
Pulse/M3
-
Noise Filter
Basic setting
-
Device ID.
-
LoraWan reporting interval.
Downlink Command
-
Change reporting interval.
-
Set Pulse Value.
-
Send Report ( Class C).
Enable / Disable showing serial port logging.